Pump Sealer Flush Coolers
MINI HEAT EXCHANGERS. COST EFFECTIVE OPTION FOR SEAL COOLING.
(1.3-3.8 Sq. Ft HX Surface Area)
- Designed to reduce high temperature liquid for longer seal life.
- 316 Stainless Steel and Copper tubing available.
- Can be disassembled with standard tools for cleaning, or replacement of damaged coils.
- Shell side pressure rating of 300 psi.
- Two Models: Type 1 & Type 2.
- Check out our latest DATA SHEET.
- FUNCTION
- PRODUCT LINE
Madden pump seal flush coolers are miniature heat exchangers designed to reduce high temperature seal flush liquids to 140°F or less. The counter flow design efficiently cools the tube side liquid (the pump’s seal flush) to optimum temperatures for maximum seal performance.
Pump seal flush coolers are available in copper and Type 316 stainless steel tube material. All Madden pump seal flush coolers disassemble with standard tools for cleaning, or replacement of damaged coils. Carbon steel shell parts are painted with grey acrylic enamel. Shell side pressure rating is 150 psi. Madden Type 2 models may be constructed using a variety of materials to meet a customer’s specific requirements. Contact the factory for a quotation for applications with special material specifications.
Why Cool a Centrifugal or Rotary Pump’s Seal Flush?
Certain types of centrifugal pumps and rotary pumps use liquid to help seal the non moving parts of the pump with the rotating shaft. This liquid aiding in the mechanical seal’s operation needs to be routinely flushed out to achieve high reliability and effective sealing performance. The API has established piping plans for the maintenance of these seals. API Plan 21, Plan 22, Plan 23, and Plan 41 all require a heat exchanger to cool the seal flush liquid before being injected into the seal. This is where Madden Engineered Products comes in. Our pump seal flush coolers are some of the most cost effective and durable liquid to liquid heat exchangers that the market has to offer.
Type 1
Type 1 pump seal flush cooler models have all the piping connections for the sample and the cooling water on the threaded cap on the top of the sample cooler. All coils are 1/4″ OD tubing, and all piping connections are 1/4″ NPT. Cooling water enters on the left and exits opposite on the right. Sample inlet connection is vertical on the top, and the cooled sample exits from the spout.
Type 2
Type 2 pump seal flush coolers offer both 1/4″ and 3/8″ OD tubing coils. Sample connections are 1/4 NPTF and are made on the top plate. Cooling water connections are 3/8″ NPTF located on both top and bottom plates.
Typically, liquid grab samples can be cooled with 1.3 square foot coil surface area models for continuous cooling of samples for instrument probes, or for steam
Miniature Heat Exchanger Types
Note: Coil side pressure ratings are based on maximum temperature of 400 deg F for copper coils and 1,000 deg F for stainless steel coils.
Part No. | Max Coil PSI | Description – type, coil surface area, coil material, coil tube size | Weight |
---|---|---|---|
SC0001 | 300 | Type1, 1.3 sf, copper coil w/ CI head, 1/4″ OD tube | 15 lbs. |
SC0002 | 300 | Type1, 2.6 sf, copper coil w/ CI head, 1/4″ OD tube | 25 lbs. |
SC0003 | 3,000 | Type1, 1.3 sf, 316 SS coil w/ SS head, 1/4″ OD tube | 15 lbs. |
SC0003A | 3,000 | Type1, 1.3 sf, 316 SS coil w/ SS head and SS body, 1/4″ OD tube | 15 lbs. |
SC0004 | 3,000 | Type1, 2.6 sf, 316 SS coil w/ SS head, 1/4″ OD tube | 25 lbs. |
SC0004A | 3,000 | Type1, 2.6 sf, 316 SS coil w/ SS head and SS body, 1/4″ OD tube | 25 lbs. |
SC101 | 300 | Type2, 1.3 sf, copper coil, 1/4″ OD tube | 25 lbs. |
SC102 | 3,850 | Type2, 1.3 sf, 316 SS coil, 1/4″ OD tube | 25 lbs. |
SC103 | 250 | Type2, 1.9 sf, copper coil, 3/8 ” OD tube | 30 bls. |
SC105 | 2,500 | Type2, 1.9 sf, 316 SS coil, 3/8″ OD tube | 30 lbs. |
SC106 | 2,500 | Type2, 3.8 sf, 316 SS coil, 3/8″ OD tube | 50 lbs. |
SC107 | 4,925 | Type2, 3.8 sf, 316 SS coil, 3/8″ OD tube | 50 lbs. |
SC108 | 4,925 | Type2, 1.9 sf 316 SS coil area, 3/8″ OD tube | 30 lbs. |
For Type 2 modes, 1/2″ to 1″ cooling water connections are available upon request. |
Note: Type 1 shell side pressure ratings are 300 PSI. Type 2 shell side pressure ratings are 15